Building Code Information

SECTION R202
DEFINITIONS

CLOSED CRAWL SPACE
A foundation without wall vents that uses air sealed walls, ground and foundation moisture control, and mechanical drying potential to control crawl space moisture. Insulation may be located at the floor level or at the exterior walls.

CONDITIONED CRAWL SPACE
A conditioned crawl space is a foundation without wall vents that encloses an intentionally heated and/or cooled space. Insulation is located at the exterior walls.

WALL VENTED CRAWL SPACE
A foundation that uses foundation wall vents as a primary means to control space moisture. Insulation is located at the floor level.

 

SECTION R318
FOAM PLASTIC

R318.2.3 Attics and crawl spaces.
Within attics and crawl spaces where entry is made only for service of utilities, foam plastic shall be protected against ignition by 1 ½ -inch –thick (38mm) mineral fiber insulation, ¼ -inch thick (6.4mm) wood structural panels, 3/8 –inch (9.5mm) particleboard, ¼ –inch (6.4mm) hardboard, 3/8 –inch (9.5mm) gypsum board, or corrosion-resistant steel having a base metal thickness of 0.016 inch (0.406). Within crawl spaces, foam plastic use is governed by R409.8.2.

 

SECTION 324
PROTECTION AGAINST TERMITES

R324.4 Crawl spaces. The use of foam plastic insulation inside of crawl spaces is governed by R409.8.1.1.

 

SECTION R408
WALL VENTED CRAWL SPACES

R408.1 Space moisture vapor control. Vented crawl space foundations shall be provided with foundation vent openings through the exterior foundation walls.

R408.1.1 Foundation vent sizing. The minimum net area of ventilation openings shall be not less than 1 square foot (0.0929 m2) for each 150 square feet (13.9 m2) of crawl space ground area.

Exception: The total area of ventilation openings may be reduced to 1/1,500 of the crawl space ground area where the required openings are placed so as to provide cross-ventilation of the crawl space. The installation of operable louvers shall not be prohibited.

R408.1.2 Foundation vent location. One foundation vent shall be within 3 feet (914mm) of each corner of the building. To prevent rainwater entry when the crawl space is built on a sloped site, the uphill foundation walls may be constructed without wall vent openings. Vent dams shall be provided when the bottom of the foundation vent opening is less than 4 inches above the finished exterior grade.

R408.1.3 Covering material. To prevent rodent entry, foundation vents shall be covered with any of the following materials provided that the ventilation holes through the covering material shall not exceed ¼ inch (6.4mm) in any direction:

1. Perforated sheet metal plates not less than 0.070 inch (1.8 mm) thick.

2. Expanded sheet metal plates not less than 0.047 inch (1.2 mm) thick.

3. Cast iron grills or grating.

4. Extruded load-bearing brick vents.

5. Hardware cloth of 0.035 inch (0.89 mm) wire or heavier.

6. Corrosion-resistant mesh, with the least dimension being 1/8 inch (3.2 mm)

R408.1.4 Drains and vent terminations. Drains (including but not limited to pressure relief and drain pans) shall terminate outdoors, to crawl space floor drains or interior pumps, and shall not intentionally discharge water into the crawl space. Crawl space drains shall be separate from roof gutter drain systems and foundation perimeter drains. Dryer vents shall terminate outdoors.

R408.1.5 Space separation. Wall vented crawl spaces shall be separated from adjoining basements, porches and garages by permanent solid wall surfaces with all utility penetrations thru the separating wall sealed. Latched, weather-stripped doors or access panels shall provide access between the crawl space and such adjoining spaces.

R408.2. Ground vapor retarder. Requires full coverage ground vapor retarders for all wall vented crawl spaces. Wall vented crawl spaces shall be protected from water entry by the evaporation of water from the ground surface. A minimum 6-mil (0.15 mm) polyethylene vapor retarder or equivalent shall be installed to nominally cover all exposed earth in the crawl space, with joints lapped not less than 12 inches. Where there is no evidence that the groundwater table can rise to within 6 inches (152 mm) of the floor of the crawl space, it is acceptable to puncture the ground vapor retarder at low spots to prevent water puddles from forming on top of the vapor retarder due to condensation. The floor of the crawl space shall be graded so that it drains to one or more low spots. Install a drain to daylight or sump pump at each low spot. Crawl space drains shall be kept separate from roof gutter drain systems and foundation perimeter drains.

R408.3 Wall dampproofing. Where the outside grade is higher than the inside grade the exterior walls shall be dampproofed from the top of the footing to the finished grade as required by R406.1.

R408.4 Site grading. Building site shall be graded to drain water away from the crawl space foundation per the requirements of R401.3.

R408.5 Insulation. The thermal insulation in a wall vented crawl space shall be placed in the floor system. Wall insulation is not allowed as the only insulation system in a wall vented crawl space. The required insulation value can be determined from Table N1102.1.

R408.6 Floor air leakage control. All plumbing, electrical, duct, plenum, phone, cable, computer wiring and other penetrations through the subfloor shall be sealed with non-porous materials, caulks or sealants. The use of Rockwool or fiberglass insulation is prohibited as an air sealant.

R408.7 Duct air leakage control. All heating and cooling ductwork located in the crawl space shall be sealed with mastic or other industry approved duct closure systems.

R408.8 Access. A minimum access opening measuring 18 inches by 24 inches (457 mm by 610 mm) shall be provided to the crawl space. See the North Carolina Mechanical Code for access requirements where mechanical equipment is located under floors.

R408.9 Removal of debris. The crawl space floor shall be cleaned of all vegetation and organic material. All wood forms used for placing concrete shall be removed before a building is occupied or used for any purpose. All construction materials shall be removed before a building is occupied or used for any purpose.

R408.10 Finished grade. The finished grade of the crawl space may be located at the bottom of the footings; however, where there is evidence that the groundwater table can rise to within 6 inches (152 mm) of the finished grade of the crawl space at the perimeter or where there is evidence that the surface water does not readily drain from the building site, the grade in the crawl space shall be as high as the outside finished grade, unless an approved drainage system is provided.

R408.11 Flood resistance. For buildings located in areas prone to flooding as established in Table R301.2 (1), the walls enclosing the crawl space shall be provided with flood openings in accordance with Section R327.2.2.

 

SECTION R409
CLOSED CRAWL SPACES

R409.1 Air sealed walls. Closed crawlspaces shall be built to minimize the entry of outdoor air into the crawl space. Specifically prohibited are foundation wall vents and wall openings to ventilated porch foundations. When outdoor packaged heating and cooling equipment is used, solid blocking and sealants shall be used to seal gaps between the exterior wall opening and the smaller supply and return ducts that pass through the opening.

R409.1.1 Caulking and sealants. Air sealing caulk, gaskets or sealants shall be applied to the foundation wall and floor assembles that separate the crawl space from outside and other ventilated areas such as joints around access door and frame, between foundation and sill plate, at penetrations for plumbing, mechanical, electrical and gas lines and at duct penetrations.

R409.1.2 Access panel/door. A minimum access opening measuring 18 inches by 24 inches (457 mm by 610 mm) shall be provided to the crawl space. See the North Carolina Mechanical Code for access requirements where mechanical equipment is located under floors. To minimize air entry, provide a tight fitting access panel/door with a latch mechanism. Access panels or doors shall be insulated to a minimum of R-2.

R409.2 Ground vapor retarder. Closed crawl spaces shall be protected from water entry by the evaporation of water from the ground surface.

R409.2.1 Ground vapor retarder. A minimum 6-mil (0.15 mm) polyethylene vapor retarder or equivalent shall be installed and secured to nominally cover all exposed earth in the crawl space, with joints lapped not less than 12 inches. Minor pockets or wrinkles that prevent total drainage across the surface of the vapor retarder are allowed. The floor of the crawl space shall be graded so that it drains to one or more low spots. Install a drain to daylight or sump pump at each low spot. Crawl space drains shall be kept separate from roof gutter drain systems and foundation perimeter drains.

R409.2.2 Liner. The ground vapor retarder may be installed as a full interior liner by sealing the edges to the walls and beam columns and sealing the seams. Single piece liner systems are approved. The top edge of the wall liner shall terminate 3 inches below the top edge of the masonry foundation wall. The top edge of liner shall be brought up the interior columns a minimum of 4 inches above the crawl space floor. The floor of the crawl space shall be graded so that it drains to one or more low spots. Install a drain to daylight or sump pump at each low spot. Crawl space drains shall be separate from roof gutter drain systems and foundation perimeter drains.

R409.2.1.1 Wall liner termite inspection gap. Provide a clear and unobstructed 3” minimum inspection gap between the top of the wall liner and the bottom of the wood sill. This inspection gap may be ignored with regards to energy performance and is not intended to create an energy penalty.

R409.2.3 Concrete floor surfacing. The ground vapor retarder may be protected against ripping and displacement by pouring an un-reinforced, minimum 2-inch thick, concrete surface directly over the vapor barrier. A base coarse of gravel or other drainage material under the ground moisture barrier is not required. The floor of the crawl space shall be graded so that the concrete surface drains to one or more low spots. Install a drain to daylight or sump pump at each low spot. Crawl space drains shall be separate from roof gutter drain systems and foundation perimeter drains.

R409.2.4 Drains and vent terminations. Drains (including but not limited to hot water tank pressure relief and drain pans, and condensate drain pipes) shall terminate outdoors, to crawl space floor drains or interior pumps, and shall not intentionally discharge water into the crawl space. Crawl space drains shall be separate from roof gutter drain systems and foundation perimeter drains. Dryer vents shall terminate outdoors.

R409.3 Wall dampproofing. Where the outside grade is higher than the inside grade the exterior walls shall be dampproofed from the top of the footing to the finished grade as required by R406.1.

R409.4 Site grading. The building site shall be graded to drain water away from the crawl space foundation per the requirements of R401.3.

R409.5 Space moisture vapor control. Closed crawl spaces shall be provided with a mechanical drying capability to control space moisture levels. The allowed methods are listed below in R409.5.1 – R409.5.5. At least one method shall be provided; however, combination systems shall be allowed.

R409.5.1 Dehumidifier. A permanently installed dehumidifier shall be provided in the crawl space. The minimum rated capacity per day is 15 pints (7.1 Liters). Condensate discharge shall be drained to daylight or interior condensate pump. Permanently installed dehumidifier shall be provided with an electrical outlet.

R409.5.2 Supply air. Supply air from the dwelling air conditioning system shall be ducted into the crawl space at the rate of 1 cubic foot per minute (0.5 L/s) per 30 square feet (4.6m2) of crawl space floor area. No return air duct from the crawl space to the dwelling air conditioning system is allowed. The crawl space supply air duct shall be fitted with a backflow damper to prevent the entry of crawl space air into the supply duct system when the system fan is not operating. An air relief vent to the outdoors may be installed. Crawl spaces with moisture vapor control installed in accordance with this section are not to be considered plenums.

R409.5.3 House air. House air shall be blown into the crawl space with a fan at the rate of 1 cubic foot per minute (0.5 L/s) per 50 square feet (4.6 m2) of crawl space floor area. The fan motor shall be rated for continuous duty. No return air duct from the crawl space back to the dwelling air conditioning system is allowed. An air relief vent to the outdoors may be installed. Crawl spaces with moisture vapor control installed in accordance with this section are not to be considered plenums.

R409.5.4 Exhaust fan. Crawl space air shall be exhausted to outside with a fan at the rate of 1 cubic foot per minute (0.5 L/s) per 50 square feet (4.6 m2) of crawl space floor area. The fan motor shall be rated for continuous duty. There is no requirement for make-up air.

R409.5.5 Conditioned space. The crawl space shall be designed as a heated and/or cooled, conditioned space with wall insulation installed per the requirements of R409.8.1. Intentionally returning air from the crawl space to space conditioning equipment that serves the dwelling shall be allowed. Foam plastic insulation located in a crawl space plenum shall be protected against ignition by an approved thermal barrier.

R409.6 Plenums. Closed crawl spaces used as supply or return air plenums for distribution of heated or cooled air shall comply with the requirements of the NC Mechanical Code. Crawl space plenums shall not contain plumbing cleanouts, gas lines or other prohibited components. Foam plastic insulation located in a crawl space plenum shall be protected against ignition by an approved thermal barrier.

R409.7 Combustion air. The air sealing requirements of a closed crawl space may result in a foundation which can not provide adequate combustion air for fuel-burning appliances; therefore, fuelburning appliances located in the crawl space such as furnaces and water heaters shall obtain combustion air from outdoors as per the NC Mechanical Code.

R409.8 Insulation. The thermal insulation in a closed crawl space may be located in the floor system or at the exterior walls. The required insulation value can be determined from Table N1102.1

Exception: Insulation shall be placed at the walls when the following condition exists: 1. The closed crawl space is designed to be an intentionally heated or cooled, conditioned space.

R409.8.1 Wall Insulation. Where the floor above a closed crawl space is not insulated, the walls shall be insulated. Wall insulation can be located on any combination of the exterior and interior surfaces and within the structural cavities or materials of the exterior crawl space walls. Wall insulation systems require that the band joist area of the floor frame be insulated. Wall insulation shall begin 3 inches below the top of the masonry foundation wall and shall extend down to 3 inches above the top of the footing or concrete floor, 3 inches above the interior ground surface or 24-inches below the outside finished ground level, whichever is less. No insulation shall be required on masonry walls of 9 inches height or less.

R409.8.1.1 Foam plastic termite inspection gap. For outside wall Section R324 governs applications. When expanded polystyrene, extruded polystyrene, polyisocyanurate, or other foam plastic insulation is installed on the inside surface of the exterior foundation walls, provisions R409.8.1.1.1 – 2 below apply.

R409.8.1.1.1 Earth floored crawl spaces. Provide a clear and unobstructed 3- inch minimum termite inspection gap between the top of the foam plastic wall insulation and the bottom of the wood sill. Because Insulation ground contact is not allowed, provide a continuous 3-inch minimum clearance gap between the bottom edge of the foam plastic wall Insulation and the earth floor surface. Refer to N1102.1.7 to determine maximum allowances for insulation gaps.

R409.8.1.1.2 Concrete floor surfaced crawl spaces. Provide a clear and unobstructed 3-inch minimum termite inspection gap between the top of the foam plastic wall insulation and the bottom of the wood sill. Provide a continuous 3-inch minimum clearance gap between the bottom edge of the foam plastic wall Insulation and the concrete floor surface. Refer to N1102.1.7 to determine maximum allowances for insulation gaps.

R409.8.1.2 Porous insulation materials. When fiberglass, rockwool, cellulose or other porous insulation materials are installed on the inside wall surface of a closed crawl space, provide a clear and unobstructed 3-inch minimum termite inspection gap between the top of the porous wall insulation and the bottom of the wood sill. To reduce wicking potential, porous insulation ground contact is not allowed in earth floored or concrete surfaced crawl spaces. Provide a continuous 3-inch minimum wicking gap between the bottom edge of the porous wall Insulation and the earth or concrete floor surface. Refer to N1102.1.7 to determine maximum allowances for insulation gaps.

R409.8.2 Foam plastic fire safety. Foam plastic insulation may be installed inside crawl spaces without a thermal cover when the insulation product has been tested in accordance with ASTM E 84 to have a flame-spread rating of not more than 25 and a smoke developed rating of not more than 450. Foam plastics that have not been tested to meet these ratings shall be protected against ignition by covering them with a thermal barrier. Acceptable thermal barriers include but are not limited to ½ inch cement board, metal foil sheets, metal foil tape, steel or aluminum metal sheets or other approved materials installed in such a manner that the foam is not exposed.

Exception: Foam plastic insulation located in closed crawl spaces used as conditioned spaces or plenums shall be protected against ignition by an approved thermal barrier.

R409.9 Floor air leakage control. All plumbing, electrical, duct, plenum, gas line and other wiring penetrations through the subfloor shall be sealed with non-porous materials, caulks or sealants. The use of rockwool or fiberglass insulation is prohibited as an air sealant.

R409.10 Duct air leakage control. All heating and cooling ductwork located in the crawl space shall be sealed with mastic or other industry approved duct closure systems.

R409.11 Removal of debris. The crawl space floor shall be cleaned of all vegetation and organic material. All wood forms used for placing concrete shall be removed before a building is occupied or used for any purpose. All construction materials shall be removed before a building is occupied or used for any purpose.

R409.12 Finished grade. The finished grade of the crawl space floor may be located at the bottom of the footings; however, where there is evidence that the groundwater table can rise to within 6 inches (152 mm) of the finished grade of the crawl space at the perimeter or where there is evidence that the surface water does not readily drain from the building site, the floor in crawl space shall be as high as the outside finished grade, unless an approved drainage system is provided.